1.0 PURPOSE:
To describe a standard operating procedure for Cleaning / Replacing the filters of various equipment.
2.0 SCOPE:
The Standard operating procedure describes in detail the method of Cleaning / Replacing the filters of various equipment.
3.0 RESPONSIBILITY:
The responsibility of cleaning the filters as per the standard operating procedure lies with the staff of rank not lower than junior utility operator under the supervision of supervisor.
The responsibility of preparing, reviewing and approving the standard operating procedure lies with the Manager - Maintenance, Head of Production and Head of QAD respectively.
4.0 METHOD:
SAMPLING BOOTH (DESPENCING BOOTH) : & FBD
4.1 Cleaning Procedure for pre filters:
4.1.1 Isolate the equipment electrically.
4.1.2 Open the filter plenum door.
4.1.3 Remove the filters from filter plenum
4.1.4 Using air jet (with not more than 1 Kg/cm2 pressure) clean the non-dust laiden face of the filter (reverse direction of air flow in system) and then from the other side.
4.1.5 Clean the filter by hosing with water as per the procedure mentioned in 4.1.4.
4.1.6 Allow the filters to dry for 2 hours.
4.1.7 Before fixing the filters check the intactness of gaskets.
4.1.8 If the gasket is found damaged, replace the gasket.
4.1.9 If the filter is found damaged during cleaning, replace the filter.
4.1.10 Record the details in Annexure-I.
4.1.11 Frequency:
Filters to be cleaned once in a month ± 2 days.
4.1.12
A tag with the following details shall be displayed at the respective equipment.
|
CLEANING/REPLACING OF PRE FILTERS |
|
Equipment No. & Capacity |
|
|
Location |
|
|
Cleaned on |
|
|
Due on |
|
|
Replaced on |
|
|
Due on |
|
|
Signature |
|
4.2 MICRONIZER:
4.2.1 Cleaning of filters.
4.2.1.1 Isolate the Air compressor electrically.
4.2.1.2 Ensure that there is no air pressure in the line.
4.2.1.3 Remove both the filter casings.
4.2.1.4 Remove both the filter elements by unscrewing the bolt provided at bottom of the filter elements.
4.2.1.5 Apply air pressure (about 2 Kg/cm2) from the non dust laiden side for above 10 min.
4.2.1.6 Re-fix the filter elements to the system. Record the details in Annexure-I.
4.2.1.7 A tag with the following details shall be displayed at the equipment.
|
CLEANING/REPLACING OF PRE FILTERS |
|
Equipment No. & Capacity |
|
|
Location |
|
|
Cleaned on |
|
|
Due on |
|
|
Replaced on |
|
|
Due on |
|
|
Signature |
|
4.2.9 Frequency:
Filter elements are to be cleaned once in a month ± 2 days and should be replaced once in a year ± 15 days.
4.3 Micron filters at DM water plant & other areas
4.3.1 Micron filters to be replaced once in a year.
4.3.2 A Tag with the following details to be tied to the Micron filters.
CLEANING/REPLACING OF PRE FILTERS |
||
Equipment No. & Capacity |
|
|
Location |
|
|
Cleaned on |
|
|
Due on |
|
|
Replaced on |
|
|
Due on |
|
|
Signature |
|
5.0 RECORDING:
The responsibility of recording the details of filter cleaning and replacement in the annexure lies with the staff of rank not lower than the supervisor.
Various equipment, cleaning, engineering