img

BREAKDOWN RECTIFICATION OF THE DIESEL GENERATOR

  To  describe a  standard operating procedure for the  breakdown   rectification of the diesel generator. 

Sharing is caring, show love and share the thread with your friends.

Description

1.0 PURPOSE:
    
    To  describe a  standard operating procedure for the  breakdown   rectification of the diesel generator. 
    
2.0    SCOPE:
    
    The standard operating procedure describes in detail the method  for the breakdown  rectification of the diesel generator. 
    
3.0    RESPONSIBILITY:
    
    The  responsibility of the breakdown  rectification  of  diesel generator lies with the staff of rank not lower than the junior  utility operator. 
        
The  responsibility of preparing, reviewing  and approving  the  standard  operating  procedure lies with the  Manager  -  Maintenance,  Head of Production and Head of QAD respectively.
    
4.0    METHOD:
    
4.1        Hard starting or does not start.

4.1.1      Checking  the Electrical system. 

4.1.1.1       If  the  battery voltage is less  than  11.0  Volts/battery,  replace with new or charge batteries. 

4.1.1.2       If the carbon brushes of the self starter are worn,  replace  with new  brushes. 

4.1.1.3       Clean  the connector of self starter with carbon  tetrachloride  to free from foreign particles. 

4.1.1.4       Remove  the  self starter contacts, service  them  by  using  emery  paper  or if the contacts are worn  out  replace  the   contacts.

4.1.1.5       Replace the distorted wires and rectify loose connection  if  any.

4.1.1.6       Check all safety cut-out switches as given below in 4.1.1.6a  to 4.1.1.6d.

4.1.1.6a     The  high water temperature cut-out should be in "NC"  position.

4.1.1.6b      The low oil pressure cut-out should be in "NO" position.

4.1.1.6c      The high RPM cut-out switch should be in "NC" position.

4.1.1.6d      Replace the cut-outs if found defective.

4.1.2         Checking of fuel system.

4.1.2.1       Open and ensure that the diesel tank outlet valve is  opened fully.

4.1.2.2       Clean  thoroughly the whole diesel line from tank to  diesel   pump  with cotton waste and observe for leakage  of  diesel.  Rectify if any.

4.1.2.3      Drian  a  1/4 L. diesel from water separator  into  a  small  waste oil bowl.

4.1.2.4       Remove  the inlet hose of diesel filter and ensure the  flow   of  diesel is flowing without any obstruction.   Remove  the  obstruction if any.

4.1.2.5       Loosen the diesel filter body head.  Remove the inlet diesel    hose of the governor and fill the hose with diesel till  the   diesel overflow from the filter body.

4.1.2.6       Tighten  the filter body head.  Fill the diesel in the  hose  till the neck level and refix the hose to the governor.

4.1.2.7       Swing the generator governor and diesel pump connecting  rod  10 to 15 times.

4.1.2.8       Measure the oil in the governor. It should be in between "H"   and "L" marking of the dip rod.

4.1.2.9       If  the governor oil is found thick or dirty,  replace  with  fresh oil.

4.1.2.10      Ensure  the  diesel solenoid is under working  condition  by  operating the  generator starting key.

4.1.3         Engine air intake.

4.1.3.1       Open  the air filter and service the air filter as given  in   this SOP steps from 4.7.1 to 4.7.17.

4.1.3.2      Open  the generator inlet air passage line and clean with  a  cloth and refix.

4.1.3.3       Remove and clean the generator breather with diesel.

4.1.4        Start the generator, if the generator does not start or hard  starting follow step No. 4.8 under mentioned.

4.2           Low oil pressure.

4.2.1         Ensure  the oil pressure gauge is in good working  condition   by replacing the gauge with another. 

4.2.2         Ensure that the hose connected to the oil pressure does  not  consist of any obstruction by removing the hose and  observing it visually.

4.2.3         Inspect oil level, the oil should  be in between "L" and "H"  markings of the dip rod.  Add oil if found  low.

4.2.4         Inspect  the condition of the oil. Replace the oil  and  oil  filters if the old oil is thick or dirty.

4.2.5         Observe the whole generator and identify  any oil leaks from  head gasket, oil sump gasket, front bearings, rear  bearings  etc. 

4.2.6         If the problem is not rectified still, follow step No.4.8. 

4.3           High water/oil temperature.

4.3.1         Inspect crank case oil level.  Add oil if found low.

4.3.2         If the crank case oil level is too high flush out oil to the  required level.

4.3.3         Inspect radiator water level.  Add DM water if found low.

4.3.4         Check  the  hardness of the radiator water  and  adjust  the  hardness  in  between 3000 PPM to 5000 PPM by  draining  the  radiator  water and changing water corrosive  resistor  element.

4.3.5         Replace the faulty gauge and thermostats.

4.3.6         Tighten the loose water pump belts and replace the defective   belts if any.

4.3.7         Replace the damaged  water hose pipes.

4.3.8         Clean the radiator fans with soap solution.                 

4.3.9         If the water temperature/oil temperature are still  raising,  follow step No.4.8. 

4.4           Generator does not attain 1500 RPM.

4.4.1         Ensure the RPM meter is under working condition. Replace  if  found faulty.

4.4.2         Check the tachometer cable if found defective replace it.

4.4.3         Check the governor vernier.  Replace the defective one.

4.4.4.        Check the governor oil level and condition.  If the level is  low  add  oil and if the oil is dirty or thick  replace  the  oil.

4.4.5         Check for the free play of connecting  rod between  governor  and fuel pump.

4.4.6         If the RPM still does not raises, follow step No.4.8. 

4.5           Voltage does not develops.

4.5.1         Check  for faulty voltmeter or selector switch  and  replace  the faulty one.

4.5.2         Rectify loose connections and defective broken wires.

4.5.3         Check  the  F1  & T1 fuses of the AVR.   Replace  the  burnt  fuses.

4.5.4         Disconnect F1 & F2 terminations from the AVR and meggar F1 &   F2  for  the  continuity of field  excitation  winding.   If  found defective follow step No.4.8 under mentioned.

4.5.5.        If  the voltage produced is out of range of 410  +3%  adjust   the "V-TRIM" till the voltage fall within the range.

4.6.         Frequency not developed.

4.6.1         Replace the faulty gauge.

4.6.2         If the frequency produced is less than 50 ± 2 or more than 52   ± 2 when the voltage and RPM are 410 ± 3% and 1500 RPM respectively, adjust QDC potentiometer present in the AVR till the  frequency fall within the range.

4.6.3         Still if the frequency is not developed/not  correct  follow  the step No.4.8. 

4.7           Servicing of the air filter element.

4.7.1         Stop the generator, if it is in running condition.

4.7.2         Loosen  clamp assembly which holds cup assembly to body  air  cleaner.

4.7.3        Remove cup assembly.

4.7.4         Loosen wing nut of outer element and remove it.

4.7.5         Remove air filter element.

4.7.6         The air filter element may be cleaned several times by using  compressed air not exceeding 30 PSI.

4.7.7         Do not  hold air  jet too close to paper element.

4.7.8         Direct air to element from inside along its folds. 

4.7.9         Repeat the step 4.7.8 for 6 times and check the element.

4.7.10        If  small holes or thinner parts are found on element   when   it  is  checked  with an electric bulb  after  cleaning  and  drying, replace  the element.

4.7.11        Do  not use element whose folds or gasket or seal  are  damaged.

4.7.12        While  cleaning  element do not heat or beat  against  something.

4.7.13        Elements  that have been cleaned several times will  finally clog  and air flow to engine would be restricted  such  elements must be replaced by a new element.

4.7.14        Fix the air filter element.

4.7.15        Place the wing nut and tighten  it.

4.7.16        Place the cup assembly.

4.7.17        Place  the  clamp assembly such that it holds body  and  cup  assembly and tighten the clamp.

4.7.18        Reset the air filter service indicator.

 


4.8           If there is any breakdown  which can not be rectified,  take  the necessary service from an authorised agency.

5.0           RECORDING

    The responsibility of recording the breakdown  in the history  card   lies with the staff of rank not  lower  than  the  maintenance supervisor. 

Tags

Diesel generator, breakdown rectification, engineering

References

View / Download